DocumentCode
2038661
Title
PD signatures of wedge type discharges in transformer insulation
Author
Berg, Gunnar ; Lundgaard, Lars E.
Author_Institution
Energy Res., SINTEF, Trondheim, Norway
fYear
2002
fDate
2002
Firstpage
211
Lastpage
214
Abstract
Discharge signatures have been studied in a combined transformer oil/impregnated paper insulation system subjected to AC high voltage. A semi-homogeneous sphere-plane electrode configuration was used to simulate wedge discharges in a power transformer. The moisture level of the impregnated paper was varied between 0.3% and 9.6%. At the highest moisture level no discharges were observed before breakdown. Below a threshold near 100 pC the discharges were almost harmless to the insulation. The variation of statistical parameters with experimental conditions was thoroughly investigated. It was found that the statistical moments skewness and kurtosis were very unstable and consequently not suitable for automatic pattern recognition.
Keywords
insulation testing; paper; partial discharge measurement; power transformer insulation; power transformer testing; transformer oil; PD signatures; insulation breakdown testing; moisture level; power transformer insulation; semi-homogeneous sphere-plane electrode configuration; statistical parameters; transformer oil/impregnated paper insulation system; wedge type discharges; Electrodes; Geometry; Moisture; Oil insulation; Partial discharges; Petroleum; Power measurement; Power transformer insulation; Power transformers; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Dielectric Liquids, 2002. ICDL 2002. Proceedings of 2002 IEEE 14th International Conference on
Print_ISBN
0-7803-7350-2
Type
conf
DOI
10.1109/ICDL.2002.1022732
Filename
1022732