    An improved method of demagnetizing high voltage power system transformers is explained theoretically and demonstrated with a prototype test instrument. Because the method relies on the time dependence of magnetic flux linkage to an applied voltage, automation is possible. The amount of time required to demagnetize a transformer is reduced and operator safety is improved. The prototype automatic demagnetizing instrument was tested on a number of different power transformers. The test results indicate that this method is very effective with accuracy as good as ±1% of full magnetization. The tests demonstrate the practicality of automatically demagnetizing a power transformer after winding resistance tests or whenever the magnetic state of a transformer core is in question.
  • Keywords
    magnetic flux; magnetisation; power transformer testing; transformer cores; transformer windings; automatic demagnetizing instrument; high voltage power system transformers; large power transformer demagnetization; magnetic flux linkage; prototype test instrument; transformer core; winding resistance tests; Couplings; Demagnetization; Magnetic cores; Magnetic domains; Magnetic flux; Phase transformers; Power transformers; Demagnetization; Magnetic flux; Power transformers; Transformer cores;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting, 2012 IEEE
  • Conference_Location
    San Diego, CA
  • ISSN
    1944-9925
  • Print_ISBN
    978-1-4673-2727-5
  • Electronic_ISBN
    1944-9925
  • Type

    conf

  • DOI
    10.1109/PESGM.2012.6344639
  • Filename
    6344639