• DocumentCode
    2045607
  • Title

    Failure of polyester spacer at low voltage equipment

  • Author

    Moradian, A.R. ; Mohseni, M. ; Estifa, F.

  • Author_Institution
    Dept. of High Voltage, Niroo Res. Inst., Tehran, Iran
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    316
  • Lastpage
    318
  • Abstract
    Arak Refinery plant of Iran confronted a number of failures of low voltage equipment. Our investigations after each event have shown that the phases of vertical busbars are connected together electrically and this caused flashover between them. Also, vertical busbars melted near the surface of spacers. Our inspections showed that degradation of polyester spacers left carbon on their surface and increased the surface conductivity between phases and neutral. So using general-purpose polyester in low voltage equipment at 50°C for long duration or higher temperature will cause surface conductivity
  • Keywords
    busbars; flashover; organic insulating materials; surface conductivity; 50 C; busbar melting; failure; flashover; low voltage equipment; polyester spacer; spacer degradation; spacer surface; surface conductivity; vertical busbars; Conductivity; Degradation; Dielectrics and electrical insulation; Inspection; Low voltage; Materials testing; Resins; Shape; Switches; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2000. Conference Record of the 2000 IEEE International Symposium on
  • Conference_Location
    Anaheim, CA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-5931-3
  • Type

    conf

  • DOI
    10.1109/ELINSL.2000.845516
  • Filename
    845516