Interaction between AVR reactive power control and high power ac-dc Converter Control as possible cause of instability
Author
Aguero, J.L. ; Arnera, P.L. ; Lastra, R.E.B. ; Molina, R. ; Biteznik, C.E. ; Barbero, S.
Author_Institution
Fac. de Ing., Univ. Nac. de La Plata, La Plata, Argentina
fYear
2012
fDate
22-26 July 2012
Firstpage
1
Lastpage
7
Abstract
Two oscillatory episodes took place in the Argentinean power system at 22:20 and 22:50, June 7th, 2008. The first one started when a 40 MVAr capacitors bank was disconnected and the second one started when a 500 kV line was disconnected. Both oscillatory episodes produced great variation of active and reactive power in several 330 kV and 500 kV power system nodes. At first sight, these oscillations seemed inter-area electromechanical oscillations, but carried out studies suggest that this oscillatory behavior could be a consequence of interaction between Reactive Power Control of generators and the ac-dc Converter Control of high power loads.
Keywords
AC-DC power convertors; electric generators; machine control; power capacitors; power system interconnection; power system stability; reactive power control; AVR reactive power control; Argentinean power system; capacitor bank; generators; high power AC-DC converter control; high power loads; inter area electromechanical oscillation; oscillatory episodes; voltage 330 kV; voltage 500 kV; Inductors; Load modeling; Oscillators; Power system stability; Reactive power control; Substations; Thyristors; AC-DC Converter Control; Automatic Voltage Control; Modeling; Power System Dynamic Stability; Power System Stabilizer; Reactive Power Control; Simulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2012 IEEE
Conference_Location
San Diego, CA
ISSN
1944-9925
Print_ISBN
978-1-4673-2727-5
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PESGM.2012.6345139
Filename
6345139
Link To Document