Practical method to determine additional load losses due to harmonic currents in transformers with wire and foil windings
Author
Driesen, Johan ; Craenenbroeck, Thierry Van ; Brouwers, Bert ; Hameyer, Kay ; Belmans, Ronnie
Author_Institution
Katholieke Univ., Leuven, Belgium
Volume
3
fYear
2000
fDate
23-27 Jan 2000
Firstpage
2306
Abstract
A method is presented to determine the additional load losses in transformers caused by harmonic currents. Several blackbox short circuit tests at different harmonic frequencies have to be conducted on existing transformers or have to be simulated in the design stage. A `K-factor´-related formula allowing for the estimation of the total augmented losses in the transformers is derived. This approach is also valid for transformers containing windings of the foil type. It is shown by means of measurements and simulations that the rise of the losses does not follow a squared dependency as it is the case with traditional wire winding transformers. An alternative K-factor definition to be used with these transformers seems to be necessary and is provided here
Keywords
eddy current losses; harmonic distortion; load (electric); power system harmonics; power transformers; transformer windings; K-factor; blackbox short circuit tests; foil windings; harmonic currents; harmonic frequencies; load losses; power transformers; total augmented losses estimation; wire windings; Circuit testing; Electrical resistance measurement; Frequency dependence; Frequency measurement; Loss measurement; Power quality; Power system harmonics; Temperature; Transformers; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Winter Meeting, 2000. IEEE
Print_ISBN
0-7803-5935-6
Type
conf
DOI
10.1109/PESW.2000.847714
Filename
847714
Link To Document