• DocumentCode
    2080950
  • Title

    Practical method to determine additional load losses due to harmonic currents in transformers with wire and foil windings

  • Author

    Driesen, Johan ; Craenenbroeck, Thierry Van ; Brouwers, Bert ; Hameyer, Kay ; Belmans, Ronnie

  • Author_Institution
    Katholieke Univ., Leuven, Belgium
  • Volume
    3
  • fYear
    2000
  • fDate
    23-27 Jan 2000
  • Firstpage
    2306
  • Abstract
    A method is presented to determine the additional load losses in transformers caused by harmonic currents. Several blackbox short circuit tests at different harmonic frequencies have to be conducted on existing transformers or have to be simulated in the design stage. A `K-factor´-related formula allowing for the estimation of the total augmented losses in the transformers is derived. This approach is also valid for transformers containing windings of the foil type. It is shown by means of measurements and simulations that the rise of the losses does not follow a squared dependency as it is the case with traditional wire winding transformers. An alternative K-factor definition to be used with these transformers seems to be necessary and is provided here
  • Keywords
    eddy current losses; harmonic distortion; load (electric); power system harmonics; power transformers; transformer windings; K-factor; blackbox short circuit tests; foil windings; harmonic currents; harmonic frequencies; load losses; power transformers; total augmented losses estimation; wire windings; Circuit testing; Electrical resistance measurement; Frequency dependence; Frequency measurement; Loss measurement; Power quality; Power system harmonics; Temperature; Transformers; Wire;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Winter Meeting, 2000. IEEE
  • Print_ISBN
    0-7803-5935-6
  • Type

    conf

  • DOI
    10.1109/PESW.2000.847714
  • Filename
    847714