DocumentCode
2099262
Title
Phase-to-ground switching transients in EHV systems
Author
Morcos, M.M.
Author_Institution
Dept. of Electr. & Comput. Eng., Kansas State Univ., Manhattan, KS, USA
fYear
1990
fDate
15-16 Oct 1990
Firstpage
203
Lastpage
210
Abstract
The author outlines the effects of unequal pole closure of circuit breakers on the magnitudes of phase-to-ground overvoltages. A model of a short section of a 500 kV line is used. Results show that the mean value of the phase-to-ground voltage increases in both directions away from the zero switching angle where it shows a minimum. The minimum is more distinct in the case of sequential switching than in the simultaneous switching mode. Risk of insulation failure is calculated for both modes of switching. Although the mean values of phase-to-ground overvoltages are less with sequential switching, higher risks of failure are encountered. This is due to the increased scatter in overvoltages indicated by their standard deviation
Keywords
circuit breakers; earthing; electrical faults; overvoltage protection; power system protection; switching; 500 kV; EHV; circuit breakers; insulation failure; phase-to-ground overvoltages; power system protection; sequential; simultaneous; switching transients; unequal pole closure; zero switching angle; Distributed parameter circuits; Insulation; Power system modeling; Power system transients; Power transmission lines; RLC circuits; Shape; Surges; Switching circuits; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Symposium, 1990., Proceedings of the Twenty-Second Annual North American
Conference_Location
Auburn, AL
Print_ISBN
0-8186-2115-X
Type
conf
DOI
10.1109/NAPS.1990.151373
Filename
151373
Link To Document