    Ice Monitoring on Overhead Transmission Lines with FBG Tension Sensor

  • Author

    Ma Guo-ming ; Li Cheng-rong ; Meng Chen-ping ; Quan Jiang-tao ; Cheng Yang-chun ; Jian, Jiang ; Tian Xiao

  • Author_Institution
    Beijing Key Lab. of High Voltage, North China Electr. Power Univ., Beijing, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Ice monitoring on the overhead transmission lines is very important to insure the power grid safe during the ice disaster. To solve the electromagnetic interference, a tension sensor based on Fiber Bragg Grating is developed to measure the tension of the power transmission line. The sensitivity of the sensor is 0.2286 pm/N calibrated with a test machine. The relative error of the load and sag, measured by the FBG sensing system, are smaller than 5% and 2% respectively based on our ice simulation system.
  • Keywords
    Bragg gratings; electromagnetic interference; fibre optic sensors; ice; optical fibres; power grids; power overhead lines; power system measurement; power system security; power transmission lines; FBG tension sensor; electromagnetic interference; fiber Bragg grating; ice disaster; ice monitoring; overhead transmission lines; power grid safe; Bragg gratings; Electromagnetic interference; Electromagnetic measurements; Fiber gratings; Ice; Monitoring; Power grids; Power measurement; Power transmission lines; Transmission line measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5448665
  • Filename
    5448665