DocumentCode
2109135
Title
Two independent methods for power transformers vibration control
Author
Aksenov, Y.P. ; Proshletsov, A.P.
Author_Institution
DIACS Co., Moscow, Russia
fYear
2011
fDate
5-8 Sept. 2011
Firstpage
487
Lastpage
494
Abstract
Power transformers´ on-line vibration control has its limits in relation to noises influence coming from mechanical components of transformer (pumps, motors); implementation of harmonics analysis helps to increase the control reliability. Implementation of capacitive currents´ to ground harmonics analysis allows increasing the reliability of vibration defects location. This becomes possible due to magnet core vibration which gives spectral lines into capacitive current with the same frequency as on-tank vibration measurements. Practical results from two independent methods are given in this paper: - capacitive current to ground harmonics analysis on transformer; - harmonics analysis of vibration velocities registered on tank.
Keywords
harmonic analysis; power transformers; vibration control; vibration measurement; capacitive currents; control reliability; ground harmonics analysis; magnet core vibration; mechanical components; motors; on-tank vibration measurements; power transformer online vibration control; pumps; vibration defects location; vibration velocities; Current measurement; Harmonic analysis; Power transformer insulation; Velocity measurement; Vibration measurement; Vibrations; Fault diagnosis; harmonics analysis; infrared surveillance; magnetic cores; predictive maintenance; transformers; vibration control; vibration measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Diagnostics for Electric Machines, Power Electronics & Drives (SDEMPED), 2011 IEEE International Symposium on
Conference_Location
Bologna
Print_ISBN
978-1-4244-9301-2
Electronic_ISBN
978-1-4244-9302-9
Type
conf
DOI
10.1109/DEMPED.2011.6063668
Filename
6063668
Link To Document