• DocumentCode
    2114187
  • Title

    Research on Scope of Environmental Influence of DC Grounding Electrode Rated ±800kV

  • Author

    Cui, Mingde ; Chu, Youqun ; Liu, Lianguang

  • Author_Institution
    Sichuan Chengdu Electr. Power Bur., Chengdu, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The reasons of environmental influence caused by DC electrode is analyzed. By analyzing the earth parameters of those DC projects which have been in operation, it presented that 1) when the current injected into the earth is 4000A, the boundary of influence caused by electrodes of ±800 kV UHVDC project is at least 20 km; 2) As for the converter station or the AC transforming plants rated HOkV or above, the site where they are located should be chosen between 20 km and 60 km off the electrode. Combining with the preparatory site Dongyang of UHVDC project from Xiluodu to Zhexi, earth parameters such as distribution of potential, step voltage in the range of 20 km have been calculated. From the results, it can be concluded that the electrode site will meet the requirement of the DC system under the condition in existence, and causes less influence to the environment.
  • Keywords
    HVDC power transmission; earthing; electric potential; DC grounding electrode; UHVDC; earth parameters; environmental influence; potential distribution; step voltage; Analog-digital conversion; Earth; Electrodes; Grounding; Pipelines; Power transmission; Satellite ground stations; Soil; Substations; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5449266
  • Filename