• DocumentCode
    2119630
  • Title

    The Aging Diagnosis of Solid Insulation for Oil-Immersed Power Transformers and Its Remaining Life Prediction

  • Author

    Lin Chaohui ; Zhang Bide ; Yuan Yuchun

  • Author_Institution
    Sch. of Electr. & Inf., Xihua Univ., Chengdu, China
  • fYear
    2010
  • fDate
    28-31 March 2010
  • Firstpage
    1
  • Lastpage
    3
  • Abstract
    The oil-filled transformer´s solid insulating life can be measured by the content of furfural dissolved in oil. The relation between furfural content and operation years is calculated. The theoretical distribution transformer attention to the value of the concentration of furfural is showed in an equation. The aging diagnosis of solid insulation can be put up. By using the average remaining life method , the oil-immersed transformer residual life prediction is showed in a formula. The result of examples show that this method can predicts exactly.
  • Keywords
    ageing; fault diagnosis; power transformer insulation; remaining life assessment; transformer oil; oil-filled transformer solid insulating life; oil-immersed power transformer residual life prediction; remaining life prediction; solid insulation aging diagnosis; theoretical distribution transformer; Aging; Degradation; Equations; Gas insulation; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Solids; Statistical distributions;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-4812-8
  • Electronic_ISBN
    978-1-4244-4813-5
  • Type

    conf

  • DOI
    10.1109/APPEEC.2010.5449486
  • Filename
    5449486