• DocumentCode
    2132696
  • Title

    A cooling-water system for the Accelerator Test Facility

  • Author

    Akemoto, Mitsuo ; Nishinomiya, Yutaro ; Suyama, Akio

  • Author_Institution
    KEK, Nat. Lab. for High Energy Phys., Ibaraki, Japan
  • fYear
    1991
  • fDate
    6-9 May 1991
  • Firstpage
    1031
  • Abstract
    A cooling-water system for the Accelerator Test Facility of the Japan Linear Collider has been constructed and operated successfully. The design, specifications and results of performance tests of the system are described. The input temperature of the cooling-water supplied to the subharmonic bunchers, prebunchers and accelerating structures is required to hold at 36.5+or-0.1 degrees C in order to insure the electrical phase stability. The temperature control for this system employs a three-way valve, a tank and line heaters.<>
  • Keywords
    linear accelerators; Accelerator Test Facility; Japan Linear Collider; accelerating structures; cooling-water system; design; electrical phase stability; input temperature; line heaters; performance tests; prebunchers; specifications; subharmonic bunchers; tank; temperature control; three-way valve; Acceleration; Control systems; Laboratories; Life estimation; Linear accelerators; Stability; System testing; Temperature control; Test facilities; Valves;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Particle Accelerator Conference, 1991. Accelerator Science and Technology., Conference Record of the 1991 IEEE
  • Conference_Location
    San Francisco, CA, USA
  • Print_ISBN
    0-7803-0135-8
  • Type

    conf

  • DOI
    10.1109/PAC.1991.164527
  • Filename
    164527