DocumentCode
2177623
Title
Prototype partial discharge simulator for use in transformers
Author
James, R.E. ; Kurusingal, J. ; Unsworth, J.
Author_Institution
Pacific Power, Sydney, NSW, Australia
Volume
2
fYear
1994
fDate
3-8 Jul 1994
Firstpage
733
Abstract
During permanent partial discharge monitoring of power transformers it will be necessary to include self checking methods in order to ensure satisfactory operation of the various measurement components. The present paper describes a device (simulator) which enables an overall assessment to be made by injecting ultrasonic and RF signals produced by an external high voltage source. Details of the simulator structure are presented and examples of its performance in the laboratory are reported. The prototype was also tested during a temporary installation in a large transformer
Keywords
charge measurement; insulation testing; partial discharges; power transformer insulation; power transformer testing; signal detection; signal processing equipment; ultrasonic applications; RF signal injection; external high voltage source; large transformer; partial discharge monitoring; partial discharge simulator; power transformers; self checking methods; ultrasonic signal injection; Laboratories; Monitoring; Partial discharge measurement; Partial discharges; Power measurement; Power transformers; Prototypes; Testing; Ultrasonic variables measurement; Virtual prototyping;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1994., Proceedings of the 4th International Conference on
Conference_Location
Brisbane, Qld.
Print_ISBN
0-7803-1307-0
Type
conf
DOI
10.1109/ICPADM.1994.414115
Filename
414115