• DocumentCode
    2196465
  • Title

    A "critical impedance" based method for identifying harmonic sources

  • Author

    Wilsun Xu ; Chun Li ; Tayjasanant, Thavatchai

  • Author_Institution
    Alberta Univ., Alta., Canada
  • fYear
    2004
  • fDate
    6-10 June 2004
  • Abstract
    Summary form only given. This paper proposes a new method to determine whether the utility or the customer side has more contribution to the harmonic currents measured at the point of common coupling. The method is inspired by the observation that the direction of harmonic reactive power, instead of active power, is a more reliable indicator on the location of dominant harmonic sources. The method needs approximate impedance information to operate. Mathematical analysis, simulation studies and field measurements have shown that this is a useful, reliable and practical solution for the harmonic source detection problem.
  • Keywords
    electric current measurement; mathematical analysis; power system harmonics; reactive power; critical impedance; field measurements; harmonic currents measurement; harmonic source identification; mathematical analysis; reactive power; Analytical models; Current measurement; Impedance; Mathematical analysis; Power system harmonics; Reactive power;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2004. IEEE
  • Conference_Location
    Denver, CO
  • Print_ISBN
    0-7803-8465-2
  • Type

    conf

  • DOI
    10.1109/PES.2004.1372959
  • Filename