Fundamental studies on vacuum circuit breaker arc quenching limits using a synthetic test circuit
Author
Betz, Thomas ; Koenig, Dieter
Author_Institution
High Voltage Lab., Tech. Univ. Darmstadt, Germany
Volume
1
fYear
1996
fDate
21-26 Jul 1996
Firstpage
376
Abstract
The aim of this work is to demonstrate the use of a synthetic test circuit with L-C resonant circuits for fundamental experimental work on vacuum circuit breakers (CB). Studies have been performed on a 36 kV-model CB at test currents of 5 and 10 kA rms aiming at separating the influence of different parameters of the transient recovery voltage (TRV) such as average rate of rise and peak value on the breaking capability. Furthermore the effect of the arcing time on the measured arc quenching limit is presented
Keywords
circuit-breaking arcs; switchgear testing; vacuum arcs; vacuum circuit breakers; 10 kA; 36 kV; 5 kA; arcing time; average rate of rise; breaking capability; medium voltage circuit breaker; synthetic test circuit; test currents; transient recovery voltage; vacuum circuit breaker arc quenching limits; Circuit breakers; Circuit testing; Power system transients; RLC circuits; Switches; Switching circuits; Transient analysis; Tuned circuits; Vacuum arcs; Voltage;