• DocumentCode
    2212257
  • Title

    Study of full scale UHV DC transmission line corona performance in corona cage

  • Author

    Wei Wang ; Li, Chengrong ; Liu, Yunpeng ; Luo, Bing ; Li, Xiaolin ; Jiang, Yitao ; An, Bing ; Wang, Yixu

  • Author_Institution
    Beijing Key Lab. of High Voltage&EMC, North China Electr. Power Univ., Beijing
  • fYear
    2008
  • fDate
    9-12 June 2008
  • Firstpage
    63
  • Lastpage
    65
  • Abstract
    To study the corona performance of full scale UHV DC transmission line, a 4 m long, 2 m times 2 m corona cage has been constructed. At the same time, a corona performance measuring system consists of audible noise level meter, EMI receiver and ultraviolet imaging telescope has been set up too. Audible noise level, radio interference level and total of ultraviolet photon of a 4 times 500 mm2 transmission line have been measured at different voltages. According to the test results, a method to determine the inception corona voltage of the full scale transmission line has been presented.
  • Keywords
    HVDC power transmission; corona; electromagnetic interference; telescopes; EMI receiver; audible noise level; audible noise level meter; corona cage; corona performance measuring system; full scale UHV DC transmission line corona performance; radiointerference level; transmission lines; ultraviolet imaging telescope; ultraviolet photon; Acoustic noise; Corona; Electromagnetic interference; Noise measurement; Optical receivers; Telescopes; Time measurement; Transmission line measurements; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2008. ISEI 2008. Conference Record of the 2008 IEEE International Symposium on
  • Conference_Location
    Vancouver, BC
  • ISSN
    1089-084X
  • Print_ISBN
    978-1-4244-2091-9
  • Electronic_ISBN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.2008.4570278
  • Filename
    4570278