• DocumentCode
    2213786
  • Title

    Lightning impulse withstand performance of a practical GIC with 5 and 10 percent SF6/N2 mixtures

  • Author

    Marsden, H.I. ; Hopkins, M.D. ; Eck, C.R., III

  • Author_Institution
    Inst. of Electr. Syst. Technol., ABB Power T&D Co. Inc., Raleigh, NC, USA
  • Volume
    2
  • fYear
    1998
  • fDate
    7-10 Jun 1998
  • Firstpage
    710
  • Abstract
    This publication presents the results of dielectric tests performed on a scale model GIC with mixtures of N2 and SF6. The purpose of these tests were to establish the allowable design stress levels for the power frequency, BIL and SIL ratings of the 420 GIC system with mixtures of N2 and SF6 where SF6 is the minority constituent. The goal was to optimize a system that would utilize less than 30% SF6 . The test model had the same geometry, conductor surface finish and insulators as the 242 kV commercial system currently offered by ABB. The results from the tests were used to establish the dielectric design parameters for the 420 kV GIC system as well as the satisfactory ratios of SF6 in N2, (SF6/N2)
  • Keywords
    SF6 insulation; gas mixtures; lightning; nitrogen; power cable insulation; 420 kV; BIL rating; GIC; N2; SF6; SF6/N2 mixture; SIL rating; design stress level; dielectric test model; lightning impulse withstand; Dielectrics; Frequency; Geometry; Insulator testing; Lightning; Performance evaluation; Power system modeling; Solid modeling; Stress; System testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1998. Conference Record of the 1998 IEEE International Symposium on
  • Conference_Location
    Arlington, VA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-4927-X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1998.694891
  • Filename
    694891