    Proposed methods to determine fault point X/R ratio for breaker evaluation

  • Author

    Dartawan, Ketut ; Pierre, Conrad St

  • Author_Institution
    Power Technol. Inc., Schenectady, NY, USA
  • fYear
    2003
  • fDate
    15-17 Sept. 2003
  • Firstpage
    213
  • Lastpage
    221
  • Abstract
    ANSI/IEEE and IEC standards provide procedures that do a fairly good job in obtaining a single fault point X/R ratio that will allow a conservative estimate of the DC component and therefore the total fault current flowing in a breaker. However, there are circuit configurations that result in overly conservative or under conservative estimates of the fault X/R ratio. This paper explores alternate methods using the information in a complex impedance network reduction and presents an alternate method that provides comparable X/R ratios and conservatism without the need to preform time consuming dual network reductions.
  • Keywords
    circuit breakers; electric impedance; short-circuit currents; AC current flow; ANSI standards; DC component estimation; DC current flow; IEC standards; IEEE standards; circuit breaker evaluation; complex impedance network reduction; fault point X/R ratio; short-circuit currents; total fault current; Circuit faults; Complex networks; Equations; Fault currents; Frequency; IEC standards; IEEE members; Impedance; Mesh networks; Preforms;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Conference, 2003. Record of Conference Papers. IEEE Industry Applications Society 50th Annual
  • ISSN
    0090-3507
  • Print_ISBN
    0-7803-7956-X
  • Type

    conf

  • DOI
    10.1109/PCICON.2003.1242617
  • Filename
    1242617