DocumentCode
2273325
Title
Protection schemes for DFIG considering rotor current and DC-link voltage
Author
Okedu, K.E. ; Muyeen, S.M. ; Takahashi, Rion ; Tamura, Junji
Author_Institution
Dept. of Electr. & Electron. Eng., Kitami Inst. of Technol., Kitami, Japan
fYear
2011
fDate
20-23 Aug. 2011
Firstpage
1
Lastpage
6
Abstract
This paper presents new schemes for protecting power converters used in doubly fed induction generator (DFIG) during a grid fault condition considering rotor current and DC-link voltage as the key points to be focused on. The different alternative methods for the protection are described, in which two schemes using the coordinated control of the d and q axis measured currents of the rotor side converter and series dynamic braking resistor (SDBR) connected to the stator are proposed and compared. The simulation results in PSCAD/EMTDC show that the two proposed schemes can eliminate the need for an expensive crowbar switch, because both could limit the rotor current of the DFIG within its nominal value during a grid fault.
Keywords
asynchronous generators; fault location; machine protection; power convertors; power grids; rotors; stators; DC-link voltage; DFIG; PSCAD-EMTDC; coordinated control; crowbar switch; doubly fed induction generator; grid fault condition; power converter protection scheme; rotor current; rotor side converter; series dynamic braking resistor; Choppers; Circuit faults; Control systems; Resistors; Rotors; Voltage control; Wind turbines;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Machines and Systems (ICEMS), 2011 International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4577-1044-5
Type
conf
DOI
10.1109/ICEMS.2011.6073453
Filename
6073453