  • Abstract
    This paper presents new schemes for protecting power converters used in doubly fed induction generator (DFIG) during a grid fault condition considering rotor current and DC-link voltage as the key points to be focused on. The different alternative methods for the protection are described, in which two schemes using the coordinated control of the d and q axis measured currents of the rotor side converter and series dynamic braking resistor (SDBR) connected to the stator are proposed and compared. The simulation results in PSCAD/EMTDC show that the two proposed schemes can eliminate the need for an expensive crowbar switch, because both could limit the rotor current of the DFIG within its nominal value during a grid fault.
  • Keywords
    asynchronous generators; fault location; machine protection; power convertors; power grids; rotors; stators; DC-link voltage; DFIG; PSCAD-EMTDC; coordinated control; crowbar switch; doubly fed induction generator; grid fault condition; power converter protection scheme; rotor current; rotor side converter; series dynamic braking resistor; Choppers; Circuit faults; Control systems; Resistors; Rotors; Voltage control; Wind turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems (ICEMS), 2011 International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4577-1044-5
  • Type

    conf

  • DOI
    10.1109/ICEMS.2011.6073453
  • Filename
    6073453