Abstract
Switching impulse breakdown values, negative and positive polarities, were measured for long oil gaps of natural ester fluid and mineral oil. A switching surge wave shape of 250×2500 μs was used for gaps of 50-150 mm between a high voltage bushing shield and a simulated tank wall (an electrode arrangement used to obtain previously published 60 Hz and 1.2×50 μs lightning impulse breakdown values). We compare these results with data obtained from 10-35 mm gaps using an electrode configuration developed by Weidmann Electrical Technology Inc. The results of this testing are consistent with previous results that showed natural ester fluid has equal or better dielectric breakdown characteristics compared to mineral oil for 10 to 150 mm gaps.
Keywords
bushings; electric breakdown; electrodes; surge protection; transformer oil; Weidmann Electrical Technology Inc; electrode configuration; long oil gaps; mineral oil; natural ester fluid; oil gaps; simulated tank wall; switching impulse; switching surge wave shape; transformers; voltage bushing shield; Breakdown voltage; Electric breakdown; Electrodes; Fluids; Insulators; Minerals; Switches;
fLanguage
English
Publisher
ieee
Conference_Titel
High Voltage Engineering and Application (ICHVE), 2012 International Conference on
Conference_Location
Shanghai
Print_ISBN
978-1-4673-4747-1
Type
conf
DOI
10.1109/ICHVE.2012.6357100
Filename
6357100
Link To Document