• DocumentCode
    2318850
  • Title

    Partial discharge monitoring system for cubicle type GIS

  • Author

    Tsurimoto, Takao ; Yoshimura, Manabu ; Muto, Hirotaka ; Arioka, Masahiro

  • Author_Institution
    Adv. Technol. R&D Center, Mitsubishi Electr. Corp., Tokyo
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    432
  • Lastpage
    436
  • Abstract
    Partial discharge (PD) monitoring system for cubicle type gas-insulated switchgear (C-GIS) filled with compressed dry air as an insulation gas was developed. The shield electrodes embedded in the solid insulator of bushings are used as PD sensors. For verification of the sensitivity of the sensors and propagation characteristics of PD pulse, artificial defects such as fixed particle on high voltage conductor and defect on creepage surface of insulator in C-GIS were used. It is clarified that the sensors had good sensitivity to PD pulse propagating along high voltage conductor in the range from VHF to UHF and that the amplitude of the sensor output had good correlation with apparent charge, pC, detected by conventional PD detector. The PD monitoring system is connected with our condition based maintenance (CBM) controller, which also monitors the abnormality of circuit breaker, disconnecting switch, gas pressure and so on, as a total diagnosis tool for our C-GIS.
  • Keywords
    bushings; circuit breakers; conductors (electric); gas insulated switchgear; partial discharges; bushings; circuit breaker; condition based maintenance controller; cubicle type GIS; diagnosis tool; gas-insulated switchgear; high voltage conductor; insulation gas; partial discharge detector; partial discharge monitoring; solid insulator; Circuit breakers; Conductors; Gas insulation; Geographic Information Systems; Monitoring; Partial discharges; Sensor phenomena and characterization; Switches; Switchgear; Voltage; Condition based maintenance; Cubicle type gas insulated switchgear; Diagnosis; Electromagnetic propagation; Electromagnetic radiation; Partial discharges; UHF; Ultra high frequency; VHF; Very high frequency;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580319
  • Filename
    4580319