  • Abstract
    This work reports on signal measurements from an imaged TR-XLPE-insulated cable at constant voltage stress, prior to the onset of partial discharge, as conventionally measured in time domain technique. Although physical events prior to partial discharge have been studied in the past, very few reports exist on signal measurements under prepartial discharge conditions. Signal intensity vs. (a) time at constant voltage, and (b) electrical tree length have been measured; signal intensity increases logarithmically with time, both prior to and after an electrical tree is observed. Tree retardant components in the insulation do not prevent such signals from appearing. Relevant reports have been summarized and relevance to aging phenomena are discussed.
  • Keywords
    XLPE insulation; ageing; partial discharge measurement; partial discharges; power cable insulation; signal detection; time-domain analysis; trees (electrical); TR-XLPE insulated cable; aging phenomena; electrical tree length; partial discharge signals; signal intensity; signal measurements; time domain technique; tree retardant components; voltage stress; Cable insulation; Electric variables measurement; Length measurement; Partial discharge measurement; Partial discharges; Retardants; Stress measurement; Time measurement; Trees - insulation; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 2004. Conference Record of the 2004 IEEE International Symposium on
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-8447-4
  • Type

    conf

  • DOI
    10.1109/ELINSL.2004.1380647
  • Filename
    1380647