• DocumentCode
    2320857
  • Title

    New PD measurement method for high power transformer PDM in service operation

  • Author

    Min Chen ; Urano, Koji ; Song-bo, Huang ; Jinno, Atsuhide

  • Author_Institution
    SE Technol. Ltd., Hong Kong
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    932
  • Lastpage
    936
  • Abstract
    Partial discharge measurement is a kind of effective condition check method for high power transformer. Normally, when a high power transformer needs to be checked by partial discharge measurement periodically, outage is required. Here, a newly developed measurement method for transformer is introduced in which a new kind of capacitive coupling sensor is applied. The sensor consists of a pair of metal plates and a high frequency CT, which can be installed at the flange of the high voltage bushing of the transformer during the transformer in commercial service operation, without any outage.
  • Keywords
    bushings; capacitive sensors; partial discharge measurement; power transformers; capacitive coupling sensor; check method; high power transformer; high voltage bushing; metal plates; partial discharge measurement; service operation; Capacitive sensors; Capacitors; Frequency; Insulators; Partial discharge measurement; Partial discharges; Power measurement; Power transformer insulation; Power transformers; Pulse transformers; PDM sensor; bushing; capacitive coupling; high frequency CT (HFCT); outage; partial discharge (PD); partial discharge measurement (PDM); pulse current; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on
  • Conference_Location
    Beijing
  • Print_ISBN
    978-1-4244-1621-9
  • Electronic_ISBN
    978-1-4244-1622-6
  • Type

    conf

  • DOI
    10.1109/CMD.2008.4580436
  • Filename
    4580436