Abstract
In this paper, a new cable voltage drop compensation scheme for ground power units is presented. The scheme is able to predict and compensate the voltage drop in an output cable by measuring the current quantities at the source. The prediction is based on an advanced cable model that includes self and mutual impedance parameters. The model predicts the voltage drop at both symmetrical and unbalanced loads. In order to determine the cable model parameters an automatic identification concept is derived. The concept is tested in full scale on a 90 kVA, 400 Hz Ground Power Unit with an output cable of 100 m. It is concluded that the performance is significant improved both with symmetrical and unsymmetrical cables and with balanced and unbalanced loads
Keywords
compensation; parameter estimation; power cables; power convertors; uninterruptible power supplies; 100 m; 400 Hz; 90 kVA; ground power units; mutual impedance; power cable parameters identification; power cable voltage drops compensation; power converter systems; self impedance; symmetrical loads; unbalanced loads; Aircraft manufacture; Airports; Cables; Current measurement; Impedance; Predictive models; Reactive power; Testing; Voltage; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Applied Power Electronics Conference and Exposition, 2002. APEC 2002. Seventeenth Annual IEEE
Conference_Location
Dallas, TX
Print_ISBN
0-7803-7404-5
Type
conf
DOI
10.1109/APEC.2002.989301
Filename
989301
Link To Document