DocumentCode
2345335
Title
Current THD reduction and anti-islanding detection in distributed generation with grid voltage distortion
Author
Mok, Hyung Soo ; Choe, Gyu Ha ; Kim, Sang Hoon ; Lee, Jeong Min ; Suh, In Young
Author_Institution
Dept. of Electr. Eng., Konkuk Univ., Seoul
fYear
2008
fDate
24-27 Nov. 2008
Firstpage
989
Lastpage
994
Abstract
Phase angle in grid-connected inverter for DPGS(Distributed Power Generation Systems) is important information for current control. When different loads are connected to PCC(Point of Common Coupling) of grid, distorted grid voltage is taken place by load utility generating distorted current. Especially, in case the grid voltage is distorted by low order frequency such as 3rd, 5th harmonic, phase angle of PLL(Phase Locked Loop) output is distorted. This paper analyze problem of current THD(Total Harmonic Distortion) due to distorted phase angle by distorted grid voltage, and propose control method compensating this problem. Also proposed anti-islanding detection method using distorted grid voltage is proposed in this paper. These proposed methods are verified by simulation and experiment.
Keywords
distributed power generation; electric current control; harmonic distortion; harmonics suppression; phase locked loops; power distribution control; antiislanding detection; current THD reduction; current control; distributed power generation systems; grid voltage distortion; grid-connected inverter; phase locked loop; Current control; Distributed control; Frequency; Harmonic analysis; Harmonic distortion; Inverters; Mesh generation; Phase distortion; Power generation; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Sustainable Energy Technologies, 2008. ICSET 2008. IEEE International Conference on
Conference_Location
Singapore
Print_ISBN
978-1-4244-1887-9
Electronic_ISBN
978-1-4244-1888-6
Type
conf
DOI
10.1109/ICSET.2008.4747151
Filename
4747151
Link To Document