• DocumentCode
    2351618
  • Title

    Transformer design and application considerations for nonsinusoidal load currents

  • Author

    Pierce, Linden W.

  • Author_Institution
    Gen. Electr. Co., Rome, GA, USA
  • fYear
    1995
  • fDate
    4-9 Jun 1995
  • Firstpage
    35
  • Lastpage
    47
  • Abstract
    The use of adjustable speed drives requires transformers capable of withstanding high levels of harmonic currents under normal operating conditions. Experience has been that overheating problems are much more common with dry type transformers than with liquid filled transformers. Transformer insulation life is determined by the hot spot temperature but confirmation of hot spot temperature rise is one performance characteristic which is ignored in industry standards. This is especially important for transformers rated for nonsinusoidal load currents. Hot spot allowances used in IEEE standards for ventilated dry type transformers were developed in 1944 and data indicates that revisions are required. The design of transformers for nonsinusoidal load currents should include an analysis of the eddy loss distribution in the windings and calculation of the hot spot temperature rise. Calculations and thermal tests giving only average winding temperature rises are not sufficient. Thermal tests with nonsinusoidal currents and measurements of hot spot temperature rises are extremely difficult on large transformers. The combination of testing and analysis may be the only economically practical approach. Analysis indicates that the dry type transformer hot spot temperature is very sensitive to the eddy loss magnitude and distribution. The UL K-factor rated dry type transformer and the recommended practices given in ANSI/IEEE C57.110 are reviewed
  • Keywords
    IEEE standards; eddy current losses; load (electric); motor drives; power transformer insulation; power transformer testing; power transformers; transformer windings; variable speed drives; ANSI/IEEE C57.110; IEEE standards; UL K-factor; adjustable speed drives; dry type transformers; eddy loss distribution; harmonic currents; hot spot temperature rise; nonsinusoidal load currents; overheating problems; transformer insulation life; transformer windings; transformers; ventilated dry type transformers; Electrical equipment industry; Manufacturing; Oil insulation; Power system harmonics; Power transformer insulation; Standards development; Temperature distribution; Temperature sensors; Testing; Variable speed drives;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Cement Industry Technical Conference, 1995. XXXVII Conference Record., 1995 IEEE
  • Conference_Location
    San Juan
  • ISSN
    1079-9931
  • Print_ISBN
    0-7803-2456-0
  • Type

    conf

  • DOI
    10.1109/CITCON.1995.514242
  • Filename
    514242