    Effect of harmonics on transformers loss of life

  • Author

    Elmoudi, A. ; Lehtonen, M. ; Nordman, Hasse

  • Author_Institution
    Power Syst. & HV Eng., Helsinki Univ. of Tech., Espoo
  • fYear
    2006
  • fDate
    11-14 June 2006
  • Firstpage
    408
  • Lastpage
    411
  • Abstract
    The use of non-linear (solid state) loads in power system has increased the awareness of the potential reduction of a transformer life due to the increased losses. Manufacturers and users have been applying IEEE C57.110-1989 which gives a conservative estimate of loading capability of transformers. In this paper, the effect of harmonics on transformers is discussed and a thermal model to predict a transformer hot spot temperature is presented. The model considers a time varying harmonic load cycle and ambient temperature. The model is applied on 31.5 MVA, 115times9times1.67%/6.3 kV ONAF transformer
  • Keywords
    IEEE standards; harmonics; losses; power transformers; thermal analysis; 31.5 MVA; 6.3 kV; IEEE C57.110-1989; ONAF transformer life; harmonics effect; hot spot temperature prediction; losses; nonlinear load; thermal model; time varying harmonic load; Eddy current testing; Eddy currents; Frequency estimation; Impedance; Power engineering and energy; Power system harmonics; Skin effect; Solid state circuits; Temperature; Transformers;