Abstract
In this paper we propose a Lagrangian coherent structures (LCS) based approach to modeling and estimation of contaminant transport and mixing in large indoor spaces in buildings. Specifically, we show how the knowledge of LCS can be exploited to enhance proper orthogonal decomposition (POD) based model reduction, sensor placement and comparing effect of different control schemes. We illustrate this approach in a three-dimensional room equipped with a mechanical ventilation system.
Keywords
building management systems; reduced order systems; ventilation; Lagrangian coherent structures; building systems; contaminant transport; dynamical systems techniques; mechanical ventilation system; model reduction; proper orthogonal decomposition; reduced order modeling; sensor placement; Buildings; Costs; Fluid dynamics; Lagrangian functions; Mechanical sensors; Reduced order systems; Shape; Space technology; Thermal management; Ventilation;