A fault location algorithm based on distributed neutral-to-ground current sensor measurements
Author
Paudel, Madhab ; Hietpas, Steven
Author_Institution
Dept. of Electr. Eng. & Comput. Sci., South Dakota State Univ., Brookings, SD, USA
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
10
Abstract
This paper presents a study of a multi-grounded three-phase four-wire distribution system and discusses a line-to-ground fault location algorithm based on real time monitoring of current levels in the neutral-to-ground path at several locations throughout the primary feeder. The measurement technique, combined with a triangulation algorithm based on an exponential curve fitting approach, suggests a fault location accuracy of approximately +/- 5 poles.
Keywords
curve fitting; distribution networks; fault location; power system faults; power system measurement; distributed neutral-to-ground current sensor measurements; exponential curve fitting; line-to-ground fault location algorithm; multi-grounded three-phase four-wire distribution system; real time monitoring; triangulation algorithm; Distribution system; EMTP simulation model; fault location algorithm; line-to-ground fault;