DocumentCode
2383904
Title
Improving Real-time Fault Analysis and Validating Relay Operations to Prevent or Mitigate Cascading Blackouts
Author
Zhang, Nan ; Kezunovic, Mladen
Author_Institution
Dept. of Electr. Eng., Texas A&M Univ., College Station, TX
fYear
2006
fDate
21-24 May 2006
Firstpage
847
Lastpage
852
Abstract
This paper proposes a new strategy at the local (substation) level, aimed at preventing or mitigating the cascading blackouts that involve relay misoperations or inadequate local diagnostic support. The strategy consists of an advanced real-time tool that combines neural network based fault detection and classification (NNFDC) algorithm and synchronized sampling based fault location (SSFL) algorithm with a relay monitoring tool using event tree analysis (ETA). The fault analysis tool provides a reference for conventional distance relay with its better performance and the relay monitoring tool provides detailed local information about the disturbances. The idea of the entire strategy is to meet several NERC recommendations to prevent blackouts using wide area protection and control
Keywords
computerised monitoring; fault location; neural nets; relay protection; substation automation; substation protection; trees (mathematics); cascading blackout mitigation; distance relay operations; event tree analysis; local diagnostic support; neural network based fault detection and classification; real-time fault analysis; relay monitoring tool; synchronized sampling based fault location; wide area protection; Classification tree analysis; Data structures; Fault detection; Monitoring; Neural networks; Power system faults; Power system protection; Protective relaying; Relays; Substations;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES
Conference_Location
Dallas, TX
Print_ISBN
0-7803-9194-2
Type
conf
DOI
10.1109/TDC.2006.1668608
Filename
1668608