DocumentCode
2384774
Title
Double layered sheath in accurate HV XLPE cable modeling
Author
Gudmundsdottir, U.S. ; De Silva, J. ; Bak, C.L. ; Wiechowski, W.
Author_Institution
Inst. of Energy Technol., Aalborg Univ., Aalborg, Denmark
fYear
2010
fDate
25-29 July 2010
Firstpage
1
Lastpage
7
Abstract
This paper discusses modelling of high voltage AC underground cables. For long cables, when crossbonding points are present, not only the coaxial mode of propagation is excited during transient phenomena, but also the intersheath mode. This causes inaccurate simulation results for high frequency studies of crossbonded cables. For the intersheath mode, the correct physical representation of the cables sheath as well as proximity affect play a large role and will ensure correct calculations of the series impedance matrix and therefore a correct simulation for the actual cable. This paper gives a new, more correct method for modelling the actual physical layout of the sheath. It is shown by comparison to field measurements how the new method of simulating the cable´s sheath results in simulations with less deviation from field test results.
Keywords
power cables; underground cables; HV XLPE cable modeling; crossbonded cables; crossbonding points; double layered sheath; high voltage AC underground cables modelling; series impedance matrix; underground cable modeling; Insulated cables; XLPE cables; modal excitation; model accuracy; modeling; power system transients; simulation; wave propagation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Society General Meeting, 2010 IEEE
Conference_Location
Minneapolis, MN
ISSN
1944-9925
Print_ISBN
978-1-4244-6549-1
Electronic_ISBN
1944-9925
Type
conf
DOI
10.1109/PES.2010.5589893
Filename
5589893