• DocumentCode
    2398190
  • Title

    Triggered Breakdown In SF/sub 6/ And SF/sub 6/ Mixtures

  • Author

    MacGregor, S.J. ; Tuema, F.A. ; Turnbull, S.M. ; Farish, O. ; Chalmers, I.D.

  • Author_Institution
    University of Strathclyde
  • fYear
    1991
  • fDate
    16-19 June 1991
  • Firstpage
    846
  • Lastpage
    851
  • Abstract
    A comprehensive study has been carried out into the breakdown characteristics (jitter, delay, dV/dt) of pulsed charged triggered spark gaps filled with SF/sub 6/ gas mixtures, for voltages up to 200kV. The influence of the combination of trigger voltage polarity and main gap voltage polarity has been investigated and the results are discussed with reference to the mechanism of discharge initiation and arc formation. A similar study has been carried out with mixtures of SF/sub 6/ and air, N/sub 2/ and He. The results emphasise the importance of trigatron voltage polarity and also reveal that several SF/sub 6/ gas mixtures possess improved switching characteristics compared to those of SF/sub 6/, without a reduction in withstand voltage. The delay time to breakdown results for SF/sub 6/ and SF/sub 6/ gas mixtures have been recorded at several pressures and compare well with predicted results according to Martin (1).
  • Keywords
    Breakdown voltage; Cables; Delay effects; Electric breakdown; Electrodes; Monitoring; Pulse generation; Signal generators; Switches; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Pulsed Power Conference, 1991. Digest of Technical Papers. Eighth IEEE International
  • Conference_Location
    San Diego, CA, USA
  • Print_ISBN
    0-7803-0177-3
  • Type

    conf

  • DOI
    10.1109/PPC.1991.733415
  • Filename
    733415