• DocumentCode
    2398251
  • Title

    Representing line voltage unbalance

  • Author

    Jeong, Seung-Gi

  • Author_Institution
    Dept. of Electr. Eng., Kwangwoon Univ., Seoul, South Korea
  • Volume
    3
  • fYear
    2002
  • fDate
    13-18 Oct. 2002
  • Firstpage
    1724
  • Abstract
    Representing the degree of voltage unbalance with the voltage unbalance factor (VUF) derived from symmetrical transformation requires complex phasor manipulations. This paper investigates various ways of representing VUF to facilitate the calculation in field applications. A formula for VUF with readily available line-to-line voltage magnitudes is derived and a straightforward graphical way of determining VUF is proposed. Various approximate methods are examined and it is shown that some alternative measures can be more effective in approximating VUF than conventional ones.
  • Keywords
    power supply quality; complex phasor manipulations; distribution systems; line voltage unbalance; line-to-line voltage magnitudes; power quality; symmetrical transformation; voltage unbalance factor; voltage unbalance measurement; Condition monitoring; Gain measurement; IEC standards; Industrial power systems; Niobium compounds; Phase measurement; Power engineering and energy; Power measurement; Power quality; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Conference, 2002. 37th IAS Annual Meeting. Conference Record of the
  • Conference_Location
    Pittsburgh, PA, USA
  • ISSN
    0197-2618
  • Print_ISBN
    0-7803-7420-7
  • Type

    conf

  • DOI
    10.1109/IAS.2002.1043766
  • Filename
    1043766