DocumentCode
2401936
Title
Coup de fouet based VRLA battery capacity estimation
Author
Pascoe, Phillip E. ; Sirisena, Harsha ; Anbuky, Adnan H.
Author_Institution
Dept. of Electr. & Electron. Eng., Univ. of Canterbury, UK
fYear
2002
fDate
2002
Firstpage
149
Lastpage
153
Abstract
The most important battery state of health (SOH) parameter is capacity. Capacity, the energy storage capability of a battery, is difficult to measure for the valve regulated lead acid (VRLA) battery. One of the most reliable approaches involves fully discharging the battery. However, this leaves the telecommunication system vulnerable to mains failure, is expensive and time consuming. Recently the authors have discovered a correlation between battery capacity, and parameters found within the voltage profile during the initial stages of discharge. This region is known as the coup de fouet. This paper presents the issues relating to the construction of a model for extracting battery capacity, knowledge from the coup de fouet. Results obtained so far indicate that this approach will form the basis of an intelligent battery management system
Keywords
ageing; condition monitoring; lead acid batteries; VRLA battery; battery capacity estimation; coup de fouet; energy storage capability; intelligent battery management system; state of health parameter; valve regulated lead acid battery; voltage profile; Battery charge measurement; Battery management systems; Data mining; Energy measurement; Energy storage; Power engineering and energy; State estimation; Temperature; Valves; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electronic Design, Test and Applications, 2002. Proceedings. The First IEEE International Workshop on
Conference_Location
Christchurch
Print_ISBN
0-7695-1453-7
Type
conf
DOI
10.1109/DELTA.2002.994604
Filename
994604