• DocumentCode
    2408632
  • Title

    Research on operating characteristic and controllability of the neutral inductance of shunt reactor

  • Author

    Xie, Yan ; Chen, Baichao

  • Author_Institution
    Sch. of Electr. Eng., Wuhan Univ., Wuhan, China
  • fYear
    2009
  • fDate
    15-16 May 2009
  • Firstpage
    260
  • Lastpage
    263
  • Abstract
    Neutral inductance of shunt reactor is an important component of shunt reactors. In this paper, the operating characteristics to suppressing frequency resonance overvoltage and reducing secondary arc current is elaborated. And the value of the neutral inductance should be determined according to the degree of compensation of the shunt reactor. So some research on the controllability of neutral inductance of shunt reactor is done. The results indicate that its value should be determined according to the maximum degree of the compensation of the shunt reactor, and not need to be set in controllable form, which narrows the range of the power regulation of the shunt reactor and requires high level of insulation of the neutral itself.
  • Keywords
    overvoltage; power control; reactors (electric); frequency resonance; high-level insulation; neutral inductance; overvoltage suppression; power regulation; secondary arc current; shunt reactor; Capacitance; Controllability; Inductance; Inductors; Insulation; Power transmission lines; Resonance; Resonant frequency; Shunt (electrical); Voltage control; degree of compensation; neutral inductance; resonance overvoltlge; secondary arc current;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Mechatronics and Automation, 2009. ICIMA 2009. International Conference on
  • Conference_Location
    Chengdu
  • Print_ISBN
    978-1-4244-3817-4
  • Type

    conf

  • DOI
    10.1109/ICIMA.2009.5156610
  • Filename
    5156610