• DocumentCode
    2414919
  • Title

    Transient recovery voltages caused by capacitor switching in wind power plants

  • Author

    Badrzadeh, Babak

  • Author_Institution
    Syst. Capability, Australian Energy Market Operator, Melbourne, VIC, Australia
  • fYear
    2012
  • fDate
    7-11 Oct. 2012
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This paper investigates transient recovery voltages across vacuum circuit breakers used for switching mechanically switched shunt capacitor banks in a wind power plant. Simulation case studies are conducted which investigate the transient recovery voltages with the original bank configuration, and a number of modified configurations. It is shown that using the original configuration, with inrush current limiting reactor in series with the capacitor, can result in a breaker failure under most onerous conditions. A number of alternative configurations are proposed which allow management of transient recovery voltages within the breaker withstand level.
  • Keywords
    capacitor switching; transients; vacuum circuit breakers; wind power plants; capacitor switching; switching mechanical switched shunt capacitor banks; transient recovery voltage; vacuum circuit breakers; wind power plants; Capacitors; Circuit breakers; Dielectric breakdown; Inductors; Surge protection; Transient analysis; Wind turbine generator; circuit breaker restrike and reignition; high frequency transients; mechanically switched capacitor; transient recovery voltages;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting (IAS), 2012 IEEE
  • Conference_Location
    Las Vegas, NV
  • ISSN
    0197-2618
  • Print_ISBN
    978-1-4673-0330-9
  • Electronic_ISBN
    0197-2618
  • Type

    conf

  • DOI
    10.1109/IAS.2012.6374100
  • Filename
    6374100