Abstract
This paper presents a new method of distinguishing the transient faults and permanent faults on transmission lines. Based on the mathematic model of an arc, the approach investigated different fault arc voltage characters and found that the harmonic contents contained in the voltage are different at different moment. By analyzing the are voltage. an algorithm based on the odd harmonic is proposed to realize the single-pole adaptive reclosure. Theoretical analysis and EMTP simulation tests show that the proposed technique is correct and valid.
Keywords
EMTP; fault diagnosis; power system faults; power system simulation; power transmission faults; power transmission lines; EMTP simulation; arc; fault arc voltage characters; harmonic contents; mathematic model; numerical algorithm; odd harmonic; permanent faults; single-pole adaptive reclosure; transient faults; transmission lines; Algorithm design and analysis; Analytical models; Arc discharges; EMTP; Harmonic analysis; Mathematical model; Mathematics; Power system transients; Transmission line theory; Voltage;