• DocumentCode
    2465567
  • Title

    Application of optimal and suboptimal current injection in twelve-pulse three-phase diode rectifiers

  • Author

    Ivkovi, Milan ; Pejovi, Predrag ; Janda, Zarko

  • Author_Institution
    Elsys Eastern Eur., Belgrade
  • fYear
    2008
  • fDate
    15-19 June 2008
  • Firstpage
    3143
  • Lastpage
    3149
  • Abstract
    Two methods of current injection applied to reduce input current THD of twelve-pulse three-phase diode rectifiers are proposed in this paper. The methods are optimal and suboptimal current injection. In the case of the optimal current injection, THD of the input currents is zero, and the currents are in phase with corresponding input voltages. In the case of suboptimal current injection, THD of the input currents is 1.016%, while the power factor is 0.9999. In comparison to conventional twelve-pulse three-phase rectifiers, that provide THD of the input currents of 15.22%, significant improvement is achieved for the price of two additional transformers with low VA rating, and dissipation of less than 2.5% of the output power in the current injection system. Proposed solutions are analyzed and compared. Both of the methods are verified by simulation. Experimental verification of the suboptimal current injection is performed on an 1.8 kW rectifier model.
  • Keywords
    autotransformers; harmonic distortion; rectifying circuits; current injection system; input current THD; suboptimal current injection; twelve-pulse three-phase diode rectifiers; Bridge circuits; Diodes; Europe; Performance analysis; Power generation; Power system modeling; Reactive power; Rectifiers; Transformers; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics Specialists Conference, 2008. PESC 2008. IEEE
  • Conference_Location
    Rhodes
  • ISSN
    0275-9306
  • Print_ISBN
    978-1-4244-1667-7
  • Electronic_ISBN
    0275-9306
  • Type

    conf

  • DOI
    10.1109/PESC.2008.4592436