Application of optimal and suboptimal current injection in twelve-pulse three-phase diode rectifiers
Author
Ivkovi, Milan ; Pejovi, Predrag ; Janda, Zarko
Author_Institution
Elsys Eastern Eur., Belgrade
fYear
2008
fDate
15-19 June 2008
Firstpage
3143
Lastpage
3149
Abstract
Two methods of current injection applied to reduce input current THD of twelve-pulse three-phase diode rectifiers are proposed in this paper. The methods are optimal and suboptimal current injection. In the case of the optimal current injection, THD of the input currents is zero, and the currents are in phase with corresponding input voltages. In the case of suboptimal current injection, THD of the input currents is 1.016%, while the power factor is 0.9999. In comparison to conventional twelve-pulse three-phase rectifiers, that provide THD of the input currents of 15.22%, significant improvement is achieved for the price of two additional transformers with low VA rating, and dissipation of less than 2.5% of the output power in the current injection system. Proposed solutions are analyzed and compared. Both of the methods are verified by simulation. Experimental verification of the suboptimal current injection is performed on an 1.8 kW rectifier model.
Keywords
autotransformers; harmonic distortion; rectifying circuits; current injection system; input current THD; suboptimal current injection; twelve-pulse three-phase diode rectifiers; Bridge circuits; Diodes; Europe; Performance analysis; Power generation; Power system modeling; Reactive power; Rectifiers; Transformers; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics Specialists Conference, 2008. PESC 2008. IEEE
Conference_Location
Rhodes
ISSN
0275-9306
Print_ISBN
978-1-4244-1667-7
Electronic_ISBN
0275-9306
Type
conf
DOI
10.1109/PESC.2008.4592436
Filename
4592436
Link To Document