• DocumentCode
    2473221
  • Title

    Research of drum level compensation method based on data fusion

  • Author

    Han, Xiaojuan ; Tian, Lihua ; Li, Junfeng

  • Author_Institution
    Dept. of Autom., North China Electr. Power Univ., Beijing
  • fYear
    2008
  • fDate
    25-27 June 2008
  • Firstpage
    5838
  • Lastpage
    5841
  • Abstract
    The temperature of condensate water has greatly influenced on differential pressure level indicator in operation, which makes level measurement not accurate. When the change of drum pressure is very little, the compensation of drum level will be accurately carried out if the average temperature of condensate water can be measured. Data fusion technology is introduced into drum level compensation of the boiler in this paper, which uses arithmetic average in batch estimation to ensure the average temperature of condensate water so that the accuracy and reliability of drum level measurement can be obviously improved compared with arithmetic average method. It is proved that the method is valid by an example.
  • Keywords
    boilers; power engineering computing; sensor fusion; batch estimation; data fusion; drum level compensation method; Arithmetic; Boilers; Containers; Current measurement; Electrical resistance measurement; Intelligent control; Level control; Level measurement; Pressure measurement; Temperature measurement; data fusion; in batch estimation; level compensation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Intelligent Control and Automation, 2008. WCICA 2008. 7th World Congress on
  • Conference_Location
    Chongqing
  • Print_ISBN
    978-1-4244-2113-8
  • Electronic_ISBN
    978-1-4244-2114-5
  • Type

    conf

  • DOI
    10.1109/WCICA.2008.4592822
  • Filename
    4592822