Effect of harmonic distortion of the supply voltage on the optimum gating angle of a TCR-type compensator
Author
Montano, J.C. ; Gutiérrez, J. ; Castilla, Miguel ; Lopez, A.
Author_Institution
IRNAS, Sevilla, Spain
fYear
1993
fDate
16-19 Aug 1993
Firstpage
123
Lastpage
128
Abstract
The authors examine the effect of harmonic distortion of the supply voltage on the optimum gating angle of a thyristor-controlled reactor-type compensator (TCR) and hence its influence on the power factor (PF) correction. The values of optimum PF are compared with those calculated using conventional formulae (which assume that the voltage waveform is purely sinusoidal). The formulae have been simplified by assuming that the switching intervals of the TCR are not affected by the distortion of the voltage supply. This assumption allows one to proceed by considering only one control parameter
Keywords
compensation; harmonic distortion; power factor correction; reactors (electric); switching circuits; thyristor convertors; TCR-type compensator; control parameter; harmonic distortion; optimum gating angle; power factor correction; supply voltage; switching intervals; thyristor-controlled reactor-type compensator; Capacitors; Equations; Harmonic distortion; Inductors; Power generation; Power system harmonics; Reactive power; Shunt (electrical); Thyristors; Voltage;