• DocumentCode
    2486049
  • Title

    Coconut oil as transformer liquid insulation — Ageing and simulated thermal and electrical faults

  • Author

    Matharage, B. S H M S Y ; Fernando, M.A.R.M. ; Tuncer, E. ; Bandara, M.A.A.P. ; Kalpage, C.S.

  • Author_Institution
    Fac. of Eng., Univ. of Peradeniya, Peradeniya, Sri Lanka
  • fYear
    2012
  • fDate
    14-17 Oct. 2012
  • Firstpage
    839
  • Lastpage
    842
  • Abstract
    This paper presents performance comparison of coconut oil as an alternative liquid insulation for transformer mineral oil during ageing and under simulated electrical and thermal fault conditions. In the ageing study, 6 wet coconut oil, 6 wet and 6 dry transformer oil samples were aged (each half as sealed and unsealed with inclusions of Cu, Al, Fe and Zn metal substances) inside an oven at 120°C. Six sample sets were taken out at three different ageing intervals i.e. 2, 5 and 7 weeks and were tested by visual inspection (color), chemical tests (interfacial tension, acidity, DGA) and electrical tests (breakdown voltage, FDS). In the electrical fault study, 2 coconut oil and 2 transformer oil samples were exposed to corona for four hours and for 20 electrical breakdowns with a point-plane gap of 15mm. In the thermal fault study, 2 coconut oil and 2 transformer oil samples were aged at 160°C for 12 hours and at 200°C for 1 hour. The DGA and FDS measurements were taken on the aged samples. FDS Results were analyzed by using Davidson-Cole Model. It was found that the coconut oil samples gave comparable results with those for transformer oil.
  • Keywords
    ageing; aluminium; chemical analysis; copper; essential oils; fault diagnosis; iron; transformer oil; zinc; Al; Cu; DGA measurement; Davidson-Cole model; FDS measurement; Fe; Zn; acidity; ageing intervals; ageing thermal-electrical faults; aluminum metal substance; breakdown voltage; chemical tests; coconut oil; color; copper metal substance; corona; electrical breakdowns; electrical tests; interfacial tension; iron metal substance; point-plane gap; simulated thermal-electrical faults; temperature 120 degC; temperature 160 degC; temperature 200 degC; time 1 hour; time 12 hour; time 2 week; time 5 week; time 7 week; transformer liquid insulation; transformer mineral oil; visual inspection; zinc metal substance; Aging; Conductivity; Dielectric liquids; Image color analysis; Oil insulation; Power transformer insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2012 Annual Report Conference on
  • Conference_Location
    Montreal, QC
  • ISSN
    0084-9162
  • Print_ISBN
    978-1-4673-1253-0
  • Electronic_ISBN
    0084-9162
  • Type

    conf

  • DOI
    10.1109/CEIDP.2012.6378911
  • Filename
    6378911