DocumentCode
2501089
Title
Minimum distance, a quick and simple method of determining the static ATC
Author
Eidiani, Mostafa ; Asadi, S.M. ; Faroji, S.A. ; Velayati, M.H. ; Yazdanpanah, D.
Author_Institution
Bojnourd Campus of Islamic Azad Univ., Bojnourd
fYear
2008
fDate
1-3 Dec. 2008
Firstpage
490
Lastpage
493
Abstract
In this paper, a quick, simple and precise method has been introduced for determining the static ATC, considering the real limitation of the network. It has also taken into account the limitation of the over load of all the elements, the over and lower voltage for all buses and terminals. In fact, (Minimum Distance) MD method is a kind of Continuation Power Flow (CPF) which converges to the response fast and with a few Load Flow (LF) from the distance between the operation point and desired point with approximation quadratic equation and only utilizes the LF to obtain the results. The algorithm presented here has been tested on 270 buses in Khorasan network and 449 buses in Iran network and has been compared with the CPF.
Keywords
approximation theory; load flow; power system analysis computing; power system stability; quadratic programming; DIgSILENT software; approximation quadratic equation; available transfer capability; continuation power flow; load flow; minimum distance method; overload limitation; static ATC; Equations; Jacobian matrices; Load flow; Power engineering and energy; Power systems; Software performance; Stability; Testing; Transformers; Voltage; CPF; DIgSILENT Software; Iran Network; Khorasan Network; Static ATC; Voltage Stability;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Conference, 2008. PECon 2008. IEEE 2nd International
Conference_Location
Johor Bahru
Print_ISBN
978-1-4244-2404-7
Electronic_ISBN
978-1-4244-2405-4
Type
conf
DOI
10.1109/PECON.2008.4762524
Filename
4762524
Link To Document