  • Title

    The grounding requirement for ground facilities against lightning

  • Author

    Chai, J.C. ; Britting, A.O., Jr.

  • Author_Institution
    Aerosp. Corp., Los Angeles, CA, USA
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    955
  • Abstract
    Using a surface wire grounding system with available measurement data as an example, this paper shows that relevant parameters, rather than a single fixed resistance-to-earth, should be included in the grounding requirement for the protection of ground facilities against lightning. It is found that the grounding system has a minimal effect on the lightning-induced damage of ground facilities for a relatively resistive ground, and Franklin rods provide no relief on the annual frequency of damage for the sample building. A natural, reasonable and logical alternative involving soil resistivity, lightning flash density, and acceptable risk which are important to lightning protection, is proposed
  • Keywords
    earthing; electric resistance measurement; electrical resistivity; lightning protection; Franklin rods; acceptable risk; annual damage frequency; building; ground facilities; grounding requirement; lightning flash density; lightning protection; lightning-induced damage; measured resistance to earth; measurement data; resistive ground; soil resistivity; surface wire grounding system; Conductivity; Electrical resistance measurement; Frequency; Grounding; Land vehicles; Lightning protection; Probability; Road vehicles; Soil measurements; Wire;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetic Compatibility, 2000. IEEE International Symposium on
  • Conference_Location
    Washington, DC
  • Print_ISBN
    0-7803-5677-2
  • Type

    conf

  • DOI
    10.1109/ISEMC.2000.874752