• DocumentCode
    2509806
  • Title

    Evaluation of service aged 35 kV TR-XLPE URD cables

  • Author

    Katz, Carlos ; Walker, Michael

  • Author_Institution
    Cable Technol. Labs. Inc., New Brunswick, NJ, USA
  • fYear
    1996
  • fDate
    15-20 Sep 1996
  • Firstpage
    411
  • Lastpage
    416
  • Abstract
    This paper provides information on aging of URD cable insulated with tree-retardant crosslinked polyethylene (TR-XLPE) compound, installed in a typical utility environment. Numerous evaluations were performed on samples of the cables aged up to 7 years in-service. AC and impulse voltage breakdown data are compared with data for similar 35 kV ethylene propylene rubber (EPR) and crosslinked polyethylene (XLPE) insulated cables removed from the same utility system. The data show that, to date, the rate of degradation of TR-XLPE cables is less than that of the EPR and XLPE insulated cables. Extrapolation of the data, assuming the same rate, indicates TR-XLPE cable will have the longest life
  • Keywords
    XLPE insulation; ageing; ethylene-propylene rubber; insulation testing; life testing; power cable insulation; power cable testing; trees (electrical); underground cables; underground residential distribution systems; 35 kV; AC voltage breakdown data; ethylene propylene rubber insulation; impulse voltage breakdown data; service aged TR-XLPE URD cables; tree-retardant crosslinked polyethylene; utility environment; Aging; Cable insulation; Degradation; Dielectric breakdown; Extrapolation; Paramagnetic resonance; Performance evaluation; Polyethylene; Rubber; Trees - insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
  • Conference_Location
    Los Angeles, CA
  • Print_ISBN
    0-7803-3522-8
  • Type

    conf

  • DOI
    10.1109/TDC.1996.547548
  • Filename