DocumentCode
2509806
Title
Evaluation of service aged 35 kV TR-XLPE URD cables
Author
Katz, Carlos ; Walker, Michael
Author_Institution
Cable Technol. Labs. Inc., New Brunswick, NJ, USA
fYear
1996
fDate
15-20 Sep 1996
Firstpage
411
Lastpage
416
Abstract
This paper provides information on aging of URD cable insulated with tree-retardant crosslinked polyethylene (TR-XLPE) compound, installed in a typical utility environment. Numerous evaluations were performed on samples of the cables aged up to 7 years in-service. AC and impulse voltage breakdown data are compared with data for similar 35 kV ethylene propylene rubber (EPR) and crosslinked polyethylene (XLPE) insulated cables removed from the same utility system. The data show that, to date, the rate of degradation of TR-XLPE cables is less than that of the EPR and XLPE insulated cables. Extrapolation of the data, assuming the same rate, indicates TR-XLPE cable will have the longest life
Keywords
XLPE insulation; ageing; ethylene-propylene rubber; insulation testing; life testing; power cable insulation; power cable testing; trees (electrical); underground cables; underground residential distribution systems; 35 kV; AC voltage breakdown data; ethylene propylene rubber insulation; impulse voltage breakdown data; service aged TR-XLPE URD cables; tree-retardant crosslinked polyethylene; utility environment; Aging; Cable insulation; Degradation; Dielectric breakdown; Extrapolation; Paramagnetic resonance; Performance evaluation; Polyethylene; Rubber; Trees - insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
Conference_Location
Los Angeles, CA
Print_ISBN
0-7803-3522-8
Type
conf
DOI
10.1109/TDC.1996.547548
Filename
547548
Link To Document