    Calculation of the remaining lifetime of power transformers paper insulation

  • Author

    Gorgan, Bogdan ; Notingher, Petru V. ; Wetzer, Jos M. ; Verhaart, Harry F A ; Wouters, Peter A A F ; Van Schijndel, Arjan ; Tanasescu, Gabriel

  • Author_Institution
    Univ. Politeh. of Bucharest, Bucharest, Romania
  • fYear
    2012
  • fDate
    24-26 May 2012
  • Firstpage
    293
  • Lastpage
    300
  • Abstract
    This paper presents the remaining lifetime calculation of power transformers paper insulation and consequently of power transformers. The calculations are performed based on two models, which are related to the thermal degradation of the cellulose winding paper insulation: the common IEC loading guide and a paper degradation model. The paper insulation model´s prediction can be improved by involving data from furfural analysis. The remaining lifetime is extracted from the fault probability (reliability) of the paper insulation. The two models are brought together, to aid the asset manager in the decision making process. A probabilistic approach is used, which can be coupled to analysis in terms of risks, benefits, costs, and availability by the asset manager.
  • Keywords
    life testing; paper; power transformer insulation; transformer windings; IEC loading guide; cellulose winding paper insulation; fault probability; paper degradation model; paper insulation reliability; power transformers paper insulation; remaining lifetime calculation; thermal degradation; Degradation; Load modeling; Oil insulation; Power transformer insulation; Uncertainty;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Optimization of Electrical and Electronic Equipment (OPTIM), 2012 13th International Conference on
  • Conference_Location
    Brasov
  • ISSN
    1842-0133
  • Print_ISBN
    978-1-4673-1650-7
  • Electronic_ISBN
    1842-0133
  • Type

    conf

  • DOI
    10.1109/OPTIM.2012.6231792
  • Filename
    6231792