• DocumentCode
    2521387
  • Title

    PD behaviour of basic test arrangements under different measurement and evaluation conditions

  • Author

    Haller, R. ; Pihera, J. ; Mraz, P. ; Kornhuber, S. ; Boltze, M.

  • Author_Institution
    Fac. of Electr. Eng., Univ. of West Bohemia in Pilsen, Pilsen, Czech Republic
  • fYear
    2011
  • fDate
    16-19 Oct. 2011
  • Firstpage
    275
  • Lastpage
    279
  • Abstract
    The PD behaviour of so called basic test arrangements as for corona discharge or other discharge sources seems to be well known from the physical side of view. On the other hand the measurement results and, in the same manner, their identification and interpretation can be different, because this is depending on the measurement or evaluation conditions. Therefore some typical corona basic arrangements representing corona needle-plane, needle-plane with insulating material and needle-sphere are investigated. The measurements are carried out under different measurement conditions especially the selected frequency range of the measuring system. For some effects the reproducibly, the voltage dependence and the changes over time of the PD behaviour are investigated. These results were evaluated using the applied and the updated version of IEC 60270. Furthermore the IEC 60270 and additional publications provide a lot of possible of the post evaluation of the measured PD signals. In this paper the most and most recognized values are compared at the well defined laboratory set ups as defined. Additional these results are compared with the results of the Pulse-Sequence-Analyzing method. The presented results show surprisingly characteristic shapes of the PD pattern, which allow the better classification of the types of PD sources and their identification respectively.
  • Keywords
    IEC standards; corona; insulating materials; measurement systems; partial discharge measurement; IEC 60270; PD behaviour; PD signals; basic test arrangements; corona basic arrangements; corona discharge; corona needle-plane; discharge sources; insulating material; insulating needle-sphere; measuring system; partial discharges; pulse-sequence-analyzing method; Bandwidth; Corona; Discharges; Frequency measurement; Materials; Partial discharges; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
  • Conference_Location
    Cancun
  • ISSN
    0084-9162
  • Print_ISBN
    978-1-4577-0985-2
  • Type

    conf

  • DOI
    10.1109/CEIDP.2011.6232650
  • Filename
    6232650