DocumentCode
2525632
Title
Feasibility study of SVC installation in a substation network for voltage fluctuation mitigation
Author
Chang, G.W. ; Su, H.J. ; Lu, H.J. ; Hsu, Y.F. ; Yang, J.S.
Author_Institution
Dept. of Electr. Eng., Nat. Chung Cheng Univ., Chiayi, Taiwan
fYear
2012
fDate
17-20 June 2012
Firstpage
494
Lastpage
498
Abstract
The operation of electric arc furnaces (EAFs) with drastic and random voltage-current characteristics creates considerable power quality problems in the connected power network. Because of the nonlinear behaviors of the EAF loads during operations, serious voltage fluctuations have been observed at busses that connect the substation transformer and cause frequent operations of the on-load tap changer (OLTC) of the transformer, which may shorten the OLTC life and affect the voltage quality. To reduce the number of switching operations of the OLTC, it is necessary to adopt mitigation solutions. This paper presents a feasibility study of installing a static var compensator (SVC) in an actual substation network supplying two large EAF loads for mitigating the voltage fluctuation and the number of OLTC operations. The effectiveness of installing the SVC at selected busses and the corresponding size are then reported.
Keywords
arc furnaces; power transformers; static VAr compensators; substations; EAF loads; OLTC operations; SVC installation; drastic voltage-current characteristics; electric arc furnaces operation; mitigation solutions; on-load tap changer; random voltage-current characteristics; static var compensator; substation network; substation transformer; voltage fluctuation mitigation; Gold; MATLAB; Reactive power; Electric arc furnace; flicker; on-load tap changer; static var compensator;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power (ICHQP), 2012 IEEE 15th International Conference on
Conference_Location
Hong Kong
ISSN
1540-6008
Print_ISBN
978-1-4673-1944-7
Type
conf
DOI
10.1109/ICHQP.2012.6381204