    Diagnosis test of power cables using a resonant test system and analysis of partial discharge on site

  • Author

    Jaramillo-Vacio, Rubén ; -Zezzatti, C. A Ochoa ; Jöns, S. ; Ledesma-Orozco, Sergio

  • fYear
    2010
  • fDate
    22-25 Aug. 2010
  • Firstpage
    114
  • Lastpage
    117
  • Abstract
    To after-laying of new-installed high voltage (HV) power cables the use of on-site non-destructive on-site testing and diagnosis of new installations of the power cables is becoming an important issue to determine the actual condition of the cable systems and to determine the future performances. An overview is presented on on-site testing using a resonant test system and partial discharge diagnosis of HV power cables with regard to on-site testing methods: AC voltage test of the insulation, diagnostic aspects using partial discharge measurement, patterns recognition using self organizing map (SOM).
  • Keywords
    installation; partial discharge measurement; power cable testing; self-organising feature maps; AC voltage test; high voltage power cables; on-site testing methods; partial discharge diagnosis; partial discharge measurement; power cable installation; resonant test system; self organizing map; Cable insulation; Partial discharge measurement; Partial discharges; Power cables; Resonant frequency; Testing; Diagnosis on site test; component; partial discharge; self organizing ma;