    Modeling of the energization of a power transformer in a 110 kV network and its validation by on site tests. Description of ferroresonance phenomena involved and means to avoid them.

  • Author

    Rioual, Michel ; Guuinic, M. Philippe ; Laval, Damien ; Schafer, Michael ; Abdelghani, Mohamed Ali ; Schafer, Nils

  • Author_Institution
    R&D Div., Electr. de France, Clamart
  • fYear
    2008
  • fDate
    20-24 July 2008
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This document presents the energization of a transformer in a 110 kV distribution network. It shows that high discrepancies in the circuit-breaker poles closing times may lead to high overvoltages, which have been confirmed by on site tests. Phenomena involved are ferroresonance ones, after the energization of the transformer, when phases A and C saturate while the breaker pole remains open on phase B during 17 ms. Recommendations in order to avoid these overvoltages are given in this paper.
  • Keywords
    circuit breakers; distribution networks; overvoltage protection; poles and towers; power transformer protection; circuit-breaker poles; ferroresonance phenomena; overvoltage avoidance; power transformer; voltage 110 kV; Circuit breakers; Circuit faults; Circuit testing; Ferroresonance; Inductance; Magnetic cores; Power transformers; Residual stresses; Surges; Transformer cores; Residual flux; circuit breakers; controlled switching; energization of power transformer; ferroresonance; inrush currents; strange attractor;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE
  • Conference_Location
    Pittsburgh, PA
  • ISSN
    1932-5517
  • Print_ISBN
    978-1-4244-1905-0
  • Electronic_ISBN
    1932-5517
  • Type

    conf

  • DOI
    10.1109/PES.2008.4596748
  • Filename
    4596748