• DocumentCode
    2548333
  • Title

    Simulation study of conventional and hybrid HVDC rectifier based on CIGRÉ benchmark model using PLL-less synchronisation scheme

  • Author

    Das, Bhaba Priyo ; Watson, Neville ; Liu, Yonghe

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Univ. of Canterbury, Christchurch, New Zealand
  • fYear
    2011
  • fDate
    6-7 June 2011
  • Firstpage
    312
  • Lastpage
    317
  • Abstract
    The objective of this paper is to compare and assess the performance of the conventional and hybrid high voltage direct current (HVDC) rectifiers based on the CIGRE benchmark model for both static and dynamic conditions with the phase lock loop (PLL) control replaced by PLL-less control. Traditional HVDC rectifier uses a 12-pulse thyristor bridge whereas the hybrid HVDC rectifier is based on one 6-pulse thyristor bridge and one 6-pulse diode bridge. Simulations are carried out in Matlab/Simulink. Some of the simulation results show that the hybrid option doesn´t look too attractive in spite of the cost savings it offers.
  • Keywords
    HVDC power transmission; phase locked loops; rectifiers; CIGRE benchmark model; PLL-less synchronisation scheme; high voltage direct current; hybrid HVDC rectifier; phase lock loop control; Bridge circuits; Firing; HVDC transmission; Harmonic analysis; Rectifiers; Synchronization; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering and Optimization Conference (PEOCO), 2011 5th International
  • Conference_Location
    Shah Alam, Selangor
  • Print_ISBN
    978-1-4577-0355-3
  • Type

    conf

  • DOI
    10.1109/PEOCO.2011.5970433
  • Filename
    5970433