Abstract
A variety of electromechanical and solid-state protective relays were tested for pickup and time-delay characteristics while tilted in several directions from vertical and while undergoing oscillatory motion. These tests showed that induction-disk and induction-cup relays were seriously affected by tilting and motion, but that hinged-armature and solid-state relays were not affected
Keywords
relay protection; electromechanical relays; induction disk relays; induction-cup relays; operating characteristics; oscillatory motion; pick-up characteristics; solid-state protective relays; time-delay characteristics; Bibliographies; Drilling; Leg; Manufacturing; Marine vehicles; Petroleum; Production; Protection; Protective relaying; Switchgear;